Fire Alarm Panel & Mimic

Fire Alarm Panel & Mimic

Fire Alarm Panel & Mimic


* FIre Alarm Panel Complied to MS 1745:Part 2: 2004
* Bomba Approved

DESCRIPTION

PROGRAM Fire Alarm Control Panel, Model : PE-FA 120L is manufactured and tested in accordance to EN 54-2 : 1997
( which is equivalent to MS1745-2 : 2004) and also conformed to the local CIFS requirement.

This controls are housed in signal red metal enclosure with glaze panel in front for clear visibility of the control and indications. The benefits of this product, it is cost saving, user friendly and it could fit into various brands of conventional detectors. This is applicable for all hospital, campus, schools, factories, commercial buildings and office buildings.


FEATURES & INDICATIONS

  • Main and D/C on Indicator
  • Main Fail Indicator
  • Battery Fail Indicator
  • Charger Fail Indicator
  • Bell Line Fail Indicator
  • Zone Fire, Fault and Isolate Indicators
  • Evacuate Switch and Indicator
  • Fire Station Isolate Switch and Indicator
  • Bell Isolate Switch and Indicator
  • Auxiliary Trip Isolate Switch and Indicator
  • Earth Fault Supervisory
  • Buzzer Mute Switch
  • Buzzer resound
  • Main on/off Switch
  • Test Lamp Switch
  • Test Zone Alarm, Fault and Isolate Switch
  • Test Battery Push Button Switch
  • Master Reset Push Button Switch
  • Pumpsets status
  • CO-2 Discharge Status

DIMENSION

No of Zones Model Normal Mimic
Size in mm ( W x H x D )
2 - 6 PE / FA 20l - 60l 510 x 535 x 204 560 x 1170 x 230
8 - 12 PE / FA 80l - 120l 510 x 586 x 204 560 x 1220 x 230
14 - 24 PE / FA 140l - 240l 610 x 775 x 204 610 x 1405 x 235


Fire Alarm Control Panel
Control and Indications Panel


TECHNICAL DATA

Power Supply Input 240V AC 50Hz
Operating / System 24V DC
Charger Auto / Trickle
Charging Rate 300mA (Trickle)
2.5A (Boost)
End of Line 8K2 Ohms
Auxiliary Output 24V, 1 Amp
CMS Output N/O Contact
Standby Mode
Master 75 mA
Per Zone (c/w Detectors) 5 mA
Alarm Mode
Master 140 mA
Per Trigger Zone 70 mA
Output Devices 200 mA
Per Bell 30 mA