Gas Fire Extinguishing Panel

PE-GA2000

Fireman Intercom System

Gas Fire Extinguishing Panel
Model : PE-GA2000



* FIre Alarm Panel Complied to MS 1745:Part 2: 2004
* Bomba Approved

PE-GA2000


Description

PROGRAM Gas Fire Extinguishing Panel, Model : PE-GA2000 is manufactured and tested in accordance to EN 54-2 : 1997 (which is equivalent to MS 1745-2 : 2004) and also conformed to local CIFS requirements.

The discharge can be automatic, using two zones double knock detection system or manual release system by using a 24V DC electrical key switch or mechanical pull bar system applied direct on the gas cylinder. This control and indicators are housed in a compact enclosure finished with signal red epoxy powder paint. This is applicable for all sub-stations, server rooms, transformer rooms, switch rooms and paint boots.


Standard Features

  • Power Source Indicators
  • Power Failure Indicators
  • Zone Fire, Fault and Isolate Indicators
  • Bell Isolate Switch and Indicator
  • Auxiliary Trip Isolate Switch and Indicator
  • Gas Isolate Switch and Indicator
  • Fault Buzzer Mute Switch
  • Master Reset Switch
  • Main on/off Switch
  • Test Battery Switch
  • Earth Fault Supervisory
  • Built-in Delay Discharge Timer (Adjustable)


DIMENSION

No of Zones Model Normal Weatherproof
Size in mm ( W x H x D )
2 PE - GA2000 430 x 370 x 170 430 x 380 x 170
4 PE - GA4000 550 x 390 x 170 550 x 400 x 170


Control and Indications Panel
Control and Indications Panel


TECHNICAL DATA

Power Supply Input 240V AC 50Hz
Operating / System 24V DC
Charger Auto / Trickle
Charging Rate 300mA (Trickle)
2.5A (Boost)
End of Line 8K2 Ohms
Auxiliary Output 24V, 1 Amp
FAP Output N/O Contact
Standby Mode
Master 75 mA
Per Zone (c/w Detectors) 5 mA
Flashing Light (Green LED) 75 mA
Alarm Mode
Master 140 mA
Per Trigger Zone 70 mA
Output Devices 200 mA
Flashing Light (Red LED) 75 mA
Per Bell 30 mA

GRP 200/400 Series

Fireman Intercom System GRP 200/400 Series

Gas Fire Extinguishing Panel
Model : PE-GRP 200s / PE-GRP 400s


* FIre Alarm Panel Complied to MS 1745:Part 2: 2004
* Bomba Approved

DESCRIPTION


PROGRAM Auto Gas Releasing Control Panel GRP 200/400 Series manufactured in accordance to MS 1745-2 : 2004 and conformed to local CIFS requirement. PE-GRP 200/400 series is a micro processor programmable user friendly control panel with a digital ammeter, voltmeter and a countdown timer displayed on the front panel. Count down timer is pre-set for 30 seconds upon two (2) activated zone. Timer can be program to required specification. Built-in power pack with an intelligent charger which allow to charge up a set of complete flat 24 volts battery and automatically cuts off charging once battery fully charge. This controls and indications are housed in a compact enclosure finished with signal red polyester epoxy powder paint. Indoor and outdoor type of enclosure are available.

Standard Features

  • Power Source Indicators
  • Power Failure Indicators
  • Zone Fire, Fault and Isolate Indicators
  • Bell Isolate Switch and Indicator
  • Auxiliary Trip Isolate Switch and Indicator
  • Gas Isolate Switch and Indicator
  • Fault Buzzer Mute Switch
  • Master Reset Switch
  • Main on/off Switch
  • Test Battery Switch
  • Earth Fault Supervisory
  • Built-in Delay Discharge Timer (Adjustable)

NEW Features

  • GAS Abort Function (Optional)
  • Digital Voltmeter & Ammeter
  • Intelligent Battery Charger
  • Digital Countdown Timer
  • Common Fault Contact
  • Low Pressure Indicator

DIMENSION

No of Zones Model Normal Weatherproof
Size in mm ( W x H x D )
2 PE - GRP 200s 430 x 370 x 170 430 x 380 x 170
4 PE - GRP 400s 550 x 390 x 170 550 x 400 x 170

Control and Indications Panel
Control and Indications Panel

TECHNICAL DATA

Power Supply Input 240V AC 50/60Hz
Operating / System 24V DC
Operating Battery 18-27.6V DC
Battery Cut Off 18V
Intelligent Charger (S1) 0.67A - 1.3A at 30%
Intelligent Charger (S5) 1.2A - 1.8A at 100%
End of Line 8K2 Ohms
Auxiliary Output 24V, 2 Amp
Alarm Signal N/O Contact
Gas Discharged Signal N/O Contact
Standby Mode
Master 75 mA
Per Zone (c/w Detectors) 5 mA
Flashing Light (Green LED) 75 mA
Alarm Mode
Master 140 mA
Per Trigger Zone 70 mA
Output Devices 200 mA
Flashing Light (Red LED) 75 mA
Per Bell 30 mA